Time-based IO basics
2.4 Hardware requirements
High-precision input/output with Time-based IO
18
Function Manual, 11/2019, A5E33454822-AC
2.4
Hardware requirements
Introduction
The properties of the hardware components required for Time-based IO are listed below.
You will also find specific modules as an example.
Requirements
Component
Properties
Examples
CPU
Isochronous mode/ PROFINET IO
IRT: provides defines response
time and high-precision plant
behavior.
•
CPU 1511-1 PN
ET 200 interface
module
Supports isochronous mode
•
ET 200SP with
IM 155-6 PN HF (as of firmware V2.1)
•
ET 200MP with
IM 155-5 PN HF
I/O module
TIO module
•
ET 200SP:
TM Timer DIDQ 10x24V
•
ET 200MP:
TM Timer DIDQ 16x24V (as of
firmware V1.0.1)