Parameter assignment/addressing
3.4 Specifying the router for a PROFINET IO device
PROFINET with STEP 7
66
Function Manual, 05/2021, A5E03444486-AL
Configuration example: Configuring a router for an IO device
The following example shows a configuration in which you configure a router at the
IO device so that the IO device reaches IP addresses in the higher-level network.
Figure 3-11 Configuration example: Configuring a router for an IO device
You have a CPU 1516-3PN/DP. The two PROFINET interfaces X1 and X2 of the CPU work in the
"IO controller" operating mode. The PROFINET interface X1 is connected with the subnet
"Production line 1". PROFINET interface X2 is connected with the subnet "Production line 2".
The two subnets "Production line 1" and "Production line 2" are each connected via a router
with the higher-level network "Superior line".
For PROFINET X1, you configure the router "Router 1" with the IP address 192.168.1.100.
The IO device (ET 200SP) in the "Production line 1" subnet adopts the router from the
IO controller.
You cannot configure a router for the PROFINET interface X2 because you have already
configured a router for the PROFINET interface X1 of the CPU.
No router is transferred by the PROFINET interface X2 to the IO device in the subnet
"Production line 2".
In order for the IO device in the subnet "Production line 2" to reach nodes in the higher-level
"Superior line", configure the router "Router 2" with the IP address 192.168.2.100 for the
IO device.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......