Applications of the F-I/O module
5.1 Digital input applications
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
48
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
Parameter assignment
Parameter name
Parameter value
Sensor evaluation
1oo2 evaluation, 2 channel - 3 wire nonequiva-
lent
Sensor supply
Internal
Short-circuit test
Enable
F-DI application mode 6
This application mode uses a two-channel sensor or two single-channel sensors with two
nonequivalent outputs in a 1oo2 voting with discrepancy evaluation. When you use an
external sensor supply, the module does not evaluate that channel for short-circuit testing.
The application mode uses the following pins:
•
Pin 2 (channels 2 and 3) is the inverted input of the nonequivalent configuration
•
Pin 4 (channels 0 and 1) is the non-inverted input of the nonequivalent configuration
Note
To incorporate F-DI application mode 6 into a SIL 3-rated application, ensure the sensors are
appropriately qualified devices.
Figure 5-9
F-DI application mode 6: External sensor supply (1oo2 evaluation of two-channel sensor with nonequivalent
outputs shown)
Parameter assignment
Parameter name
Parameter value
Sensor evaluation
1oo2 evaluation, 2 channel - 3 wire nonequiva-
lent
Sensor supply
External
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......