PROFIenergy
8.4 IO-Link operating mode
CM 4xIO-Link 4xM12 (6ES7147-5JD00-0BA0)
39
Equipment Manual, 04/2021, A5E32352322-AE
8.4
IO-Link operating mode
Display
Switching off the supply voltage 1U
S
also switches off the associated port status LED Cn.
Response to error detection
All channels which are set to "PE_MODE_PROCEED" and "PE_MODE_LAST_VALUE" in pause
mode report errors as in productive operation.
The following conditions apply to all channels (ports) which switch to a different pause mode
("PE_MODE_SHUTDOWN" and "PE_MODE_SUBST_VALUE"):
• Switching off the supply voltage U
Sn
(port) upon starting the "pause" does not lead to
generation of the alarms "Wire break" and "Short circuit".
• Error detection is not possible during the "pause" (no IO-Link device communication):
–
Alarms for errors already pending before the "pause" are retained.
–
After the "pause" is over, the error status is updated and incoming/outgoing errors are
reported correspondingly.
Mode parameter
The following table shows the "Mode" parameter.
Table 8- 3
Mode parameter
Element Code
Explanation
Mode
0
D
: PE_MODE_PROCEED
Proceed at "pause"
• Value status "GOOD"
1
D
: PE_MODE_SHUTDOWN
Switch off at "pause"
• Supply voltages 1U
S
and 2U
A
off
1
• Pause substitute value (input): 0
B
• Value status "BAD"
3
D
: PE_MODE_LAST_VALUE
Last value at "pause"
• Pause substitute value: Last input value
• Value status "BAD"
4
D
: PE_MODE_SUBST_VALUE
Substitute value at "pause"
• Supply voltages 1U
S
and 2U
A
off
1
• Pause substitute value (input): 0
B
• Value status "BAD"
1
Supply voltage 1U
S
of the assigned port is switched off. Result: The IO-Link device is no longer
supplied with voltage.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......