OPC UA communication
9.4 Using the S7-1500 CPU as an OPC UA client
Communication
Function Manual, 05/2021, A5E03735815-AJ
331
Consistency check
Finally, check the consistency of the read/write list or method list.
1.
Select the list that you want to check.
2.
Click the "Consistency check" button above the "OPC UA client interface" area.
A green check mark indicates an error-free assignment of the tags or methods to the
corresponding elements of the server interface.
You can assume that the data exchange between client and server and method calls operate
without problem in runtime.
In the event of an error a list appears in the Inspector window. From this list you can jump to
the respective error.
During the consistency check, STEP 7 checks:
•
Whether all elements that you use in the respective list are also present in the server.
•
Do the data types used match?
•
For methods: Do the number, name, order, and data types of method arguments match?
9.4.6
Determine server interface online
With STEP 7 (TIA Portal) you can determine the interface of an OPC UA server online. This
provides information on which tags of a connected OPC UA server you can read or set (write)
with OPC UA clients. It also provides information on which server methods of the OPC UA
server are available for OPC UA clients.
If you are work offline you can create the interface of the OPC UA server by means of an OPC
UA XML file. The address space of the server is described in the OPC UA XML file, see: Export
OPC UA XML file (Page 217).
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......