Parameters/address space
4.2 Parameters
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
20
Equipment Manual, 08/2021, A5E48753535-AB
4.2
Parameters
Parameters of the analog input module AI 4xRTD/TC 4xM12
Specify the module properties with the various parameters in the course of the parameter
assignment of the module with STEP 7. The following table lists the configurable parameters.
The effective range of the configurable parameters depends on the type of configuration. The
following configurations are possible:
•
Distributed mode on PROFINET IO
•
Distributed mode with PROFIBUS DP
•
Central operation with an ET 200SP CPU
NOTICE
Match of encoder and parameters
The default setting of the analog inputs is voltage measurement (± 80 mV).
Make sure that the connected encoders and the selected parameters match.
Parameters and presettings of the analog input module.
The table below shows the PROFINET IO and PROFIBUS DPparameters for the analog input
module AI 4xRTD/TC 4xM12 for configuration with GSD file.
Table 4- 2
Configurable parameters and their default (GSD)
Parameter
Value range
Default
Effective range with config-
uration software e.g. STEP 7
(TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Temperature unit
•
Degrees Celsius
•
Degrees Fahrenheit
•
Kelvin
Degrees Celsius Module
Module
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......