VK104 (K5.6)

TECHNICAL DATA

Page 1 of 6

Form No. F_033514     19.11.18   Rev 19.4

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

1.  DESCRIPTION

The Micromatic

®

 Viking Standard Response Horizontal Sidewall Sprinkler VK104 is 

a small thermosensitive glass bulb spray sprinkler available with various finishes and 

temperature ratings to meet design requirements. The special Polyester and Electroless 

Nickel PTFE (ENT) coatings can be used in decorative applications where colors are 

desired. In addition, the ENT and Polyester coatings have been investigated for 

installation in corrosive  environments and are listed/approved as indicated in the Approval 

Chart(s).

2.  LISTINGS AND APPROVALS*

cULus Listed: Category VNIV
FM Approved: Class Series 2000
LPCB Approved 
CE Certified: 

Standard EN 12259-1, EC-certificate of constancy of 

performance 0832-CPR-S0021, EC-Certificate of Conformmity 0832-

CPD-2001

China Approval: 

Approved according to China GB standard.

NOTE:

Other international approval certificates are available upon reqeust.

*  Refer to the approval charts and design criteria for Listing and approval requirements that 

must be followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar) 

Rated to 175 psi (12 bar) water working pressure

Factory tested hydrostatically to 500 psi (34.5 bar)

Nominal K-Factor: 5.6 U.S. (80.6 metric*)

*  Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: 2-1/2” (64 mm)

Material Standards:

Frame Casting: Brass UNS-C84400 or QM Brass

Deflector: Copper UNS-C19500 

Bulb: Glass, nominal 5 mm diameter

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Screw: Brass UNS-C36000

Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400.

For ENT Coated Sprinklers:

 

Belleville Spring-Exposed, Screw and Pip Cap-ENT Coated

For Polyester Coated Sprinklers:

 

Belleville Spring-Exposed

Ordering Information:

 Refer to Table 1.

4.  INSTALLATION

Refer to appropriate NFPA Installation Standards.

5.  OPERATION

During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and 

sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern 

to extinguish or control the fire.

6.  INSPECTIONS, TESTS AND MAINTENANCE

Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.

7.  AVAILABILITY

The Micromatic

®

 Viking Standard Response Horizontal Sidewall Sprinkler VK104 is available through a network of domestic and 

international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Horizontal Sidewall

For Light Hazard Occupancies Only

Replaces Form F_033514 Rev 19.3

(Revised China Approval; Obsoleted 19777)

Summary of Contents for 10171

Page 1: ... 500 psi 34 5 bar Nominal K Factor 5 6 U S 80 6 metric Metric K factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 1 2 64 mm Material Standards Frame Casting Brass UNS C84400 or QM Brass Deflector Copper UNS C19500 Bulb Glass nominal 5 mm diameter Bel...

Page 2: ...h the following temperature ratings 155 F 68 C Lt Brown Wax 175 F 79 C Brown Wax 200 F 93 C Brown Wax 286 F 141 C Dk Brown Wax5 Accessories Sprinkler Wrenches see Figure 1 A Standard Wrench Part No 21475M B B Standard Wrench for Wax Coated Sprinklers Part No 10896W B C Socket Wrench for Recessed Pendent Sprinklers Part No 13655W B A 1 2 ratchet is required not available from Viking D Socket Wrench...

Page 3: ...iking website for the latest edition of this technical data page www vikinggroupinc com Figure 3 Recessed Sprinkler Installation A 1 2 ratchet is required which is not available from Viking Step 1 Carefully slide the wrench sideways around the deflector ensuring engagement with the sprinkler wrench flats Step 2 Carefully press the wrench onto the sprinkler wrench flats Figure 1 Sprinkler Wrenches ...

Page 4: ...l K factor Overall Length Listings and Approvals3 Refer also to UL Design Criteria NPT BSPT U S metric2 Inches mm cULus4 LPCB MED CE8 China Approval 12995 VK104 1 2 5 6 80 6 2 1 2 64 A1Z B1X B2X C4Z E4Y A1Z B2Z C19 C1Z8 12988 VK104 15 mm 5 6 80 6 2 1 2 64 A1Z B1X B2X C4Z E4Y A1Z B2Z C19 C1Z8 2023010 VK104 15 mm 5 6 80 6 2 1 2 64 D3 D3 NOTICE Product Below No longer offered 10224 VK104 1 2 5 6 80 6...

Page 5: ...so with the provisions of governmental codes ordinances and standards whenever applicable Approval Chart 1 FM Micromatic Viking Standard Response Horizontal Sidewall Sprinkler VK104 Maximum 175 PSI 12 Bar WWP Sprinkler Base Part Number1 SIN Thread Size Nominal K factor Overall Length FM Approvals3 Refer also to UL Design Criteria NPT BSPT U S metric2 Inches mm 12995 VK104 1 2 5 6 80 6 2 1 2 64 A1Y...

Page 6: ...e latest edition of this technical data page www vikinggroupinc com Surface Mounted Escutcheon 2 1 4 58 mm 2 1 16 52 mm 2 1 4 57 mm 2 1 4 57 mm 1 7 16 37 mm 1 7 16 37 mm 1 7 16 37 mm Maximum Maximum Maximum Minimum Minimum Minimum Model E 1 Recessed Escutcheon Wall Opening Size Maximum 2 1 2 64 mm Minimum 2 5 16 57 mm Model E 3 Recessed Escutcheon Model E 2 Recessed Escutcheon Figure 4 Installatio...

Page 7: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 8: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 9: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 10: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 11: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Reviews: