Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
23
Parameters/address space
4
All connected fail-safe I/O must have their operating properties configured by the
STEP 7 Safety configuration software. You have the responsibility to ensure that no
unconfigured modules are connected in a fail-safe automation system.
F-Parameters
You must assign the PROFIsafe addresses (F-destination address together with F-source
address) to the F-module before you put it into operation as follows:
•
You define the F-source address using the "Central F-source addresses" parameter in the F-
CPU.
•
An F-destination address unique throughout the project's hardware configuration is
automatically assigned for each F-module. You can manually change the F-destination
addresses assigned in the hardware configuration.
You can find further information on F-parameters such as the F-monitoring time, the
PROFIsafe address assignment (F-source address, F-destination address), F-parameter
signature (with or without addresses) and the F-I/O DB in the
SIMATIC, Industrial Software,
SIMATIC Safety - Configuring and Programming, Programming and Operating Manual
on the
Internet (
https://support.industry.siemens.com/cs/ww/en/view/54110126
.
4.1
Configuring module I/O properties
To configure fail-safe module I/O properties, follow these steps:
1.
Select the image of a fail-safe I/O device (on the Device view or Device overview) and view
the module's "Properties" tab.
2.
On the "Properties" view, select the "General" tab.
3.
Select a property category in the left-side property tree and then set values in the right-side
property fields.
4.
A successful compile and download of your hardware configuration to one of the following
CPUs automatically puts your new configuration settings in the I/O modules:
–
ET 200pro F
–
ET 200SP F
–
S7-1200 F
–
S7-1500 F
–
Prior generation S7-300 F and S7-400 F
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......