OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
294
Function Manual, 05/2021, A5E03735815-AJ
Definition of SimaticAlarmConditionType
The following figure shows how events of the type "SimaticAlarmConditionType" are defined
by a series of expansions to the OPC UA "BaseEventType".
Description of the event fields for SimaticAlarmConditionType
The following table contains information about the fields of SimaticAlarmConditionType for
stateful and acknowledgeable alarms, which are added to the event fields such as
SimaticEventType. Fields that are optional according to OPC UA and are not used by the OPC
UA server of the CPU are omitted. You can also find a description of the fields in the
specification OPC 10000-9: OPC Unified Architecture, Part 9: Alarms & Conditions, Release
1.04.
BrowsePath
DataType
Explanations
ConditionClassId
NodeId
Node IDs for SystemConditionClassType,
ProcessConditionClassType or BaseCondi-
tionClassType are possible
ConditionClassName
LocalizedText
Display name of the ConditionClassId
Retain
Boolean
Indicates that the alarm is still relevant for
OPC UA clients (set if alarm is still pending
and not acknowledged).
Comment
LocalizedText
•
Most recent comment entered using the
"AddComment" or "Acknowledge" meth-
od.
•
ZERO after a server restart and if no
comment was entered.
Comment.SourceTimestamp UtcTime
Time stamp for the last change of the com-
ment field
AckedState
LocalizedText
"Acknowledged" or "Unacknowledged"
AckedState.Id
Boolean
Set, if acknowledged
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......