Wiring
3.3 Connecting the M12 eCoding plug
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
21
Note
ET-Connection/supply voltage
Installing a supply voltage cable in an ET-connection socket or an ET-connection cable in the
supply voltage loop-through socket can destroy the module.
Observe the correct wiring of the M8 sockets for ET-Connection and the supply voltage.
3.3
Connecting the M12 eCoding plug
The eCoding plug (6ES7194-6KB01-0AA0) stores the PROFIsafe addresses that you assign to
the F-DI 4/F-DQ 2 Fail-Safe module:
eCoding Plug
(side view)
F-DI 4/F-DQ 2 with eCoding Plug Attached
(front view)
F-DI 4/F-DQ 2 with eCoding Plug Attached
(side view)
The eCoding plug stores the following information:
•
PROFIsafe source address
•
PROFIsafe destination address
•
Address validity information
The eCoding plug occupies the X40 M12 socket, utilizing a B-coded plug. You use the
eCoding plug to facilitate module replacement.
The eCoding plug stores assigned PROFIsafe source and destination addresses. The "Assign
PROFIsafe address option" is selected in STEP 7 during the F-DI 4/F-DQ 2 Fail-Safe module set-
up. The module checks the PROFIsafe addresses stored in the eCoding plug against the
PROFIsafe reference addresses provided to the module during start-up parameterization.
Protection mechanisms prevent you from damaging the eCoding plug or an I/O channel due
to attempted plugging of the eCoding plug into an I/O M12 socket or plugging of an I/O M12
cable into the X40 socket.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......