Substitute value
With this parameter, you set substitute values for the analog outputs.
The table below shows the permitted value ranges for the substitute values:
Table 4- 3
Permissible substitute values for the output ranges
Output type
Output range
Valid substitute value
Current
±10 V
0 V to 10 V
1 V to 5 V
-32512 to 32511
0..32511
-6912 to 32511
Voltage
±20 mA
0 mA to 20 mA
4 mA to 20 mA
-29031..29030
0..29030
-692 to 29376