Cable shielding
4.4 Connecting the cable shield for bus cables
Designing interference-free controllers
Function Manual, 06/2014, A5E03461486-AB
21
4.4
Connecting the cable shield for bus cables
In the S7-1500, ET 200MP and ET 200SP systems, the cable shields of PROFIBUS and
PROFINET cables are connected to the existing bus connection elements. Cable shield and
shield support are thus galvanically connected to each other. If the connector is plugged into
the module, the coupled interferences are diverted via the module carrier to the ground.
There is no need for the otherwise standard connection of the shield at the cabinet entry.
The following figure shows examples of the shield connection for various bus connection
elements.
①
BusAdapter BA 2xRJ45 for ET 200SP
②
PROFIBUSconnector, 9-pin D-Sub
③
PROFINETconnector RJ45
④
Shield support of respective connector
Figure 4-5
Shield connection for bus connection elements
Reference
For more information on installing the connectors, refer to the "Connecting PROFINET IO
BusAdapter BA 2xRJ45 to the interface module" chapter of the system manual ET 200SP
Distributed I/O System (
http://support.automation.siemens.com/WW/view/en/58649293
) and
to the supplied product information.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......