Communication with the redundant system S7-1500R/H
14.6 Open User Communication with the redundant system S7-1500R/H
Communication
420
Function Manual, 05/2021, A5E03735815-AJ
Open User Communication via a system IP address of the redundant system S7 1500R/H
If you set up the connection via a system IP address, then communication always takes place
via the primary CPU.
Recommendation: Always use a system IP address for Open User Communication.
Open User Communication via a device IP address of the redundant system S7 1500R/H
In redundant mode, the redundant system can establish or terminate connections and send
or receive data via every device IP address.
If you set up the connection via a device IP address, then communication takes place via the
associated CPU. In the event of the failure of the CPU, then the entire communication via the
device IP addresses of this CPU fails.
Setting up a connection via a system IP address
The following describes how to establish a connection to another CPU via a system IP address
of a PROFINET interface of the redundant S7 1500R/H system.
You set up the connection in the user program of the redundant system S7-1500R/H with a
TSEND_C instruction. You create a corresponding TRCV_C instruction in the user program of
the other CPU.
The procedure is described using the example of a TCP connection between the S7-1500R/H
redundant system and a CPU 1516-3PN/DP.
Requirements
•
A redundant system S7 1500R/H, e.g. 2 CPUs 1513 1PN
•
System IP address of the PROFINET interface X1 is enabled.
•
CPU 1516-3PN/DP
•
The PROFINET interfaces X1 of the CPUs 1513R and the PROFINET interface X2 of the CPU
1516-3PN/DP are located in the same subnet.
Figure 14-10 Example configuration for TCP-connection
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......