Communication with the redundant system S7-1500R/H
14.6 Open User Communication with the redundant system S7-1500R/H
Communication
Function Manual, 05/2021, A5E03735815-AJ
419
14.6
Open User Communication with the redundant system
S7-1500R/H
The following table shows which protocols of the Open User Communication you can use for
the S7-1500R/H redundant system and the matching system data types and instructions.
Table 14- 1 Protocols, system data types and usable instructions for Open User Communication with
the redundant system S7-1500R/H
Protocol
System data type
Instructions
TCP
•
TCON_QDN
•
TCON_IP_v4
Establish connection and send/receive
data via:
•
TSEND_C/TRCV_C or
•
TCON, TSEND/TRCV or
•
TCON, TUSEND/TURCV
(connection can be terminated via
TDISCON)
ISO-on-TCP
•
TCON_IP_RFC
UDP
•
TCON_IP_v4
•
TADDR_Param
•
TADDR_SEND_QDN
•
TADDR_RCV_IP
Establish connection and send/receive
data via:
•
TSEND_C/TRCV_C
•
TUSEND/TURCV/TRCV
(connection can be terminated via
TDISCON)
Modbus TCP
•
TCON_IP_v4
•
TCON_QDN
•
MB_CLIENT
•
MB_RED_CLIENT
•
MB_SERVER
•
MB_RED_SERVER
14.6.1
Setting up the connection of the Open User Communication with the
redundant S7-1500R/H system
Introduction
The S7-1500R/H redundant system can communicate with other devices via Open User
Communication.
You set up the connections in the user program, e.g. via the "TSEND_C" instruction. The
S7-1500R/H redundant system does not support configured connections.
You can either set up the connections either via the device IP addresses or via the system IP
addresses of the PROFINET interfaces.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......