PROFIenergy
7.2 Behavior of the digital output module
Digital output module DQ 8x24VDC/2A 8xM12 (6ES7142-5AF00-0BA0)
26
Equipment Manual, 08/2021, A5E36683723-AB
7.2
Behavior of the digital output module
Display
The channel status LEDs are directly affected by the signal level at the socket.
Response to error detection
All channels that are in pause mode on "PE_MODE_PROCEED" report their diagnostic status as
in productive mode.
The following applies for all channels which switch to a different pause mode:
•
During the "pause", error detection of "Short circuit" is not possible:
–
Alarms for errors already pending before the "pause" are retained.
–
After the "pause" is over, the error status is updated and incoming/outgoing errors are
reported correspondingly.
Mode parameter
The following table shows the "Mode" parameter.
Table 7- 1
Mode parameter
Element Code
Explanation
Mode
0
D
: PE_MODE_PROCEED
Proceed at "pause"
•
Value status "GOOD"
1
D
: PE_MODE_SHUTDOWN
Switch off at "pause"
•
Pause substitute value: 0
B
•
Value status "BAD"
3
D
: PE_MODE_LAST_VALUE
Last value at "pause"
•
Pause substitute value: Last output value is main-
tained
•
Value status "BAD"
4
D
: PE_MODE_SUBST_VALUE
Substitute value at "pause"
•
Pause substitute value: Configured pause substi-
tute value is output
•
Value status "BAD"
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......