Maintenance
8.3 Resetting a module
IO-Link I/O modules
50
System Manual, 08/2021, A5E48755395-AB
8.3
Resetting a module
Introduction
With "Restore Factory Setting", the IO-Link I/O module is set to the delivery condition. All
information that was saved internally on the IO-Link I/O module is deleted.
Options for resetting
You can reset the IO-Link I/O module in S7-PCT.
You have two different possibilities for this.
•
"Application Reset"
•
"Restore Factory Setting"
Result after "Application Reset"
The "Application Reset" command resets the application-specific parameters to the default
values. The identification parameters of the module remain unchanged.
The command is not followed by a module restart or a communication interruption.
Result after "Restore Factory Setting"
The "Restore Factory Setting" command causes three different actions. The actions are
dependent on the data backup setting on the IO-Link master.
•
"None":
The default parameters of the IO-Link I/O module are loaded. The IO-Link I/O module
performs a restart.
•
"Restore":
The saved parameters at the time of the backup are loaded. The IO-Link I/O module
performs a restart.
•
"Backup&Restore":
The parameters that were in the IO-Link I/O module before the "Restore Factory Setting"
command are loaded. The IO-Link I/O module performs a restart.
Requirement
An online connection must exist to reset an IO-Link I/O device.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......