Interrupts/diagnostics alarms
5.3 Diagnostics alarms
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Equipment Manual, 08/2021, A5E32350124-AG
37
Table 5- 8
Diagnostics alarms - for the measuring range: Pt100 and Ni100
Diagnostics
alarm
Error code Meaning
Remedy
Wire break
6
H
Impedance of encoder circuit too
high
Use a different encoder type or
modify the wiring, for example,
using cables with larger cross-
section
Wire break between the module
and sensor
Connect the cable
Channel not connected (open)
•
Deactivate diagnostics
•
Connect the channel
•
Deactivate channel
High limit violat-
ed
7
H
Value is above overrange.
Correct interplay between mod-
ule and sensor
Low limit violat-
ed
8
H
Value is below underrange.
Correct interplay between mod-
ule and sensor
Parameter error 10
H
Module parameter assignment is
faulty
Correct the parameter assign-
ment
Hardware inter-
rupt lost
16
H
At least one hardware interrupt
could not be signaled because
too many hardware interrupts are
pending.
Correct the program or the pro-
cess
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......