PROFINET with the redundant S7-1500R/H system
6.9 Configuring media redundancy (MRP) for a configuration with the redundant S7-1500R/H system
PROFINET with STEP 7
Function Manual, 05/2021, A5E03444486-AL
309
6.9
Configuring media redundancy (MRP) for a configuration with
the redundant S7-1500R/H system
Requirements
•
Redundant S7-1500R/H system
•
All devices in the ring support the media redundancy protocol MRP.
•
IO devices are assigned to the redundant S7-1500R/H system.
Figure 6-14 Example configuration: Configuring MRP for S7-1500R/H
MRP role of the CPUs of the redundant S7-1500R/H system
As soon as you create a redundant S7-1500R/H system in STEP 7, STEP 7 automatically assigns
the MRP role "Manager (auto)" to the PROFINET interfaces X1 of both CPUs.
Defining the MRP role for additional devices of the ring in STEP 7
To specify the media redundancy for additional devices in the ring, follow these steps:
1.
In the network view of STEP 7, select the PROFINET interface X1 of one of the two CPUs of
the redundant S7-1500R/H system.
2.
In the Inspector window navigate to "Properties" > "General" > "Advanced options" > "Media
redundancy".
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......