PROFIenergy
7.2 Behavior of the digital input module
DI 8x24VDC 8xM8 (6ES7141-5BF00-0BA0)
26
Equipment Manual, 08/2021, A5E32349579-AD
Mode parameter
The following table shows the "Mode" parameter.
Table 7- 1
Mode parameter
Element Code
Explanation
Mode
0
D
: PE_MODE_PROCEED
Proceed at "pause"
•
Value status "GOOD"
1
D
: PE_MODE_SHUTDOWN
Switch off at "pause"
•
Encoder supply U
S
switched off
1
•
Pause substitute value: 0
B
•
Value status "BAD"
3
D
: PE_MODE_LAST_VALUE
Last value at "pause"
•
Encoder supply U
S
switched off
1
•
Pause substitute value: Last input value
•
Value status "BAD"
4
D
: PE_MODE_SUBST_VALUE
Substitute value at "pause"
•
Encoder supply U
S
switched off
1
•
Pause substitute value: Configured pause substi-
tute value
•
Value status "BAD"
1
As there is only one encoder supply U
S
for all channels, the supply can only be switched off at
"pause" if no channel is configured in PE_MODE_PROCEED.