Connecting
5.3 Operation of the ET 200AL on grounded/non-grounded infeed
Distributed I/O system
System Manual, 08/2021, A5E31861578-AJ
41
Components and protective measures
Various components and protective measures are stipulated for setting up a complete plant.
The types of components and the degree to which the protective measures are mandatory
depend on the IEC regulation that applies to your plant setup.
The following table shows the components of the electrical configuration with reference to
the previous figure and compares the IEC regulations.
Table 5- 1
Components of electrical configuration
Reference to
illustration
IEC 60364
(DIN VDE 0100)
IEC 60204
(DIN VDE 0113)
Disconnection ele-
ment for controller,
sensors, and actuators
①
Main switch
Disconnector
Short-circuit / over-
load protection
②
Single-pole protection of
circuits
Secure all incoming supply
cables with a circuit breaker
(24 V DC/4 A).
Secure with one pole with a
grounded secondary circuit
Cable protection
③
Protection of cables and
wires against overcurrent
-
Insulation monitoring
In the following situations, you must provide insulation monitoring.
•
When configuring the ET 200AL distributed I/O system with non-grounded reference
potential
•
When hazardous system conditions may occur due to errors
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......