Connecting
5.7 Wiring
Distributed I/O system
System Manual, 08/2021, A5E31861578-AJ
51
5.7
Wiring
Connection
Connect all cables to the front side of the modules:
•
Supply voltage and ET-Connection to the 4-pin M8 round sockets and M8 round
connectors
•
Signal lines to the 3-pin M8 or 4/5-pin M12 round sockets
•
Fieldbus lines to the 4/5 pole M12 round sockets and M12 round connectors
Note
Color coding
The sockets for ET-Connection and the power supply of the modules are color-coded. These
colors correspond to the colors of the offered cables.
Requirement
Wire the modules with the supply voltage off.
Required tools
If you are not using pre-assembled cables, you need the following tools:
•
Stripping tool
•
Screwdriver to wire the connection plugs
•
Stripping Tool for ET-Connection
Required accessories when connecting the supply voltage
You need the following accessories:
•
Cables
–
Pre-assembled power cable, M8, 4-pin, or
–
Flexible 4-wire copper cable (wire cross section: 0.25 to 0.5 mm
2
)
•
4-pin M8 connection plug