Counting
4.1 Configuration method 2xCount
Digital input/Digital output module DIQ 16x24VDC/0.5A 8xM12 (6ES7143-5AH00-0BA0)
38
Equipment Manual, 08/2021, A5E38688112-AD
Parameter
Value range
Default
Scope
Behavior Counter 0 (DI5), Counter 1 (DI7)
Behavior DI
•
Digital input without
function
•
Counting direction
Digital input
without function
Counter
Input delay DI
•
0.05 ms
•
0.1 ms
•
0.4 ms
•
0.8 ms
•
1.6 ms
•
3.2 ms
•
12.8 ms
•
20 ms
3.2 ms
Counter
1
= Is ignored if DI5/DI7 is parameterized as the direction input.
2
= Cannot be parameterized with GSD file
The table below shows the parameters of the freely assignable Channels 8...15.
Table 4- 9
Parameter freely assignable Channels 8..15
Parameter
Value range
Default
Scope
Freely assignable channel
•
DI
•
DQ
DI
Channel
Substitute value channel
•
0
•
1
0
Channel
(digital outputs)
Input delay
•
1.6 ms
•
3.2 ms
•
12.8 ms
•
20 ms
3.2 ms
Channel
(digital inputs)
See also
Pin assignment (Page 33)