Interrupts/diagnostics alarms
5.2 Interrupts
IO-Link digital input/digital output module DIQ 4+DQ 4x24VDC/0,5A 8xM8 (6ES7143-5BF00-0BL0)
Equipment Manual, 08/2021, A5E47925743-AB
21
5.2
Interrupts
The DIQ 4+DQ 4x24VDC/0,5A 8xM8 IO-Link digital input / digital output module supports
diagnostic interrupts.
Diagnostic interrupt
The digital input/digital output module generates a diagnostic interrupt at the following
events:
•
Short-circuit of encoder supply to ground
•
Short-circuit of outputs to ground
•
Load voltage 2L+ missing or too low
5.3
Diagnostics alarms
For each diagnostic event, a diagnostics alarm is issued and the DIAG LED flashes red on the
digital input/output module.
You can read out the diagnostics alarms, for example, from the port status of the IO-Link
master. You can evaluate the error codes with the user program.
Table 5- 4
Diagnostics alarms, their meanings and corrective measures
Diagnostics alarm Error code Meaning
Remedy
Short-circuit
1
0x7710
Short-circuit of an encoder sup-
ply to ground
•
Eliminate the short-circuit
0x7711
Short-circuit of an output to
ground
Load voltage 2L+
missing
0x5112
Load voltage 2L+ missing or too
low
•
Check the supply voltage
•
Check the module
1
= If a short-circuit of the encoder supply to ground is detected, the diagnostic alarm "Short-circuit" is
always output. This alarm is output even if all channels are configured as outputs.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......