OPC UA communication
9.2 Security at OPC UA
Communication
Function Manual, 05/2021, A5E03735815-AJ
189
9.2.7.3
Setting and loading GDS parameters
The following describes the settings required for the certificate update.
Requirement
•
STEP 7 (TIA Portal) V17 or higher
•
S7-1500 CPU firmware V2.9 or higher
•
Timet/date of the CPU is set (generally applies to certificate-based communication)
•
The OPC UA server is enabled.
•
At least one endpoint with the "Sign & Encrypt" security policy must be configured. The
partner must use this endpoint.
•
An authenticated user with sufficient function rights is configured
The user must have a role that has the function right "Manage certificates".
This function right, in turn, has the following requirements:
–
Project protection
must be enabled in the project tree: Project tree: "Security settings
> Settings > Project protection".
–
In the "OPC UA > General" area of the CPU settings, the following general user
management setting must be enabled: "Enable additional user management via project
security settings"
The Users and roles with OPC UA function rights (Page 238) section describes how to set the
function rights.
Activating GDS
When the requirements listed above are met, you must still enable the GDS:
1.
In the Inspector window (CPU parameters), go to the "OPC UA > Server > General" area.
2.
Enable the "Enable Global Discovery Services (Push)" option.
Determining the certificate store used
Certificates that are managed using GDS, are in a different memory area than the certificates
that are downloaded via the TIA Portal (STEP 7). When GDS is enabled, the OPC UA server of
the CPU should also use certificates from the certificate store whose certificates are managed
during runtime.
1.
In the CPU settings, go to the "OPC UA > Server > Security > Certificates" area.
2.
Select the option "Use certificates managed by certificate management server during
runtime".
The other option (use certificates configured and downloaded using TIA Portal) uses the
certificates that are downloaded to the CPU from the TIA Portal with the configuration in
CPU STOP. Certificates or trust lists cannot be updated in this certificate store during
runtime.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......