Parameters/address space
4.2 Parameters
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
25
Channel
Value range
Default
Parameter re-
assignment in
RUN
Scope
Interval for short-circuit test
•
12.8 ms
•
25.6 ms
•
51.2 ms
•
102.4 ms
•
204.8 ms
•
409.6 ms
•
819.2 ms
25.6 ms
no
Channel
Duration of short-circuit test
•
1.6 ms
•
3.2 ms
•
6.4 ms
•
12.8 ms
1.6 ms
no
Channel
Channel n, n+2
Sensor evaluation
•
1oo1 evaluation
•
1oo2 evaluation:
–
2 channel equiv-
alent
–
2 channel -
3 wire non-
equivalent
–
2 channel -
4 wire non-
equivalent
1oo2 evaluation, 2
channel equivalent
no
Channel
Discrepancy behavior
•
Supply value 0
•
Supply last valid
value
Supply value 0
no
Channel
Discrepancy time
5 ms to 30 s
5 ms
no
Channel
Reintegration after discrepancy error •
Test 0-Signal not
necessary
•
Test 0-Signal neces-
sary
Test 0-Signal not nec-
essary
no
Channel
Channel n
Activated
•
disable
•
enable
enable
no
Channel
Input filters
•
0.8 ms
•
1.6 ms
•
3.2 ms
•
6.4 ms
•
12.8 ms
6.4 ms
no
Channel
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......