Digital input/digital output module DIQ 4+DQ 4x24VDC/0.5A 8xM8 (6ES7143-5BF00-0BA0)
Equipment Manual, 08/2021, A5E32349882-AD
17
Parameters/address space
4
4.1
Parameters
The following table shows the parameters for the DIQ 4+DQ 4x24VDC/0.5A 8xM8 digital
input/digital output module.
Table 4- 1
Parameters
Parameters
Value range
Default
Scope
Diagnostics: Missing load voltage 2L+ •
Disable
•
Enable
Disable
Module
Diagnostics: Short-circuit to ground
•
Disable
•
Enable
Disable
Module
(Short-circuit of
encoder supply or
of the output to
ground)
Freely assignable channel 0 … 3
•
DI
•
DQ
DI
Channel
Reaction to CPU/master STOP
•
Shut down
•
Keep last value
•
Output substi-
tute value
Shut down
Module
(digital outputs)
Substitute value channel 0 … 7
•
0
•
1
0
Channel
(digital outputs)