Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
20
Equipment Manual, 08/2021, A5E32350124-AG
Parameters/address space
4
4.1
Measurement types and measuring ranges
The table below indicates which measuring range is configurable.
Table 4- 1
Measurement type and measuring ranges
Measurement type
Measuring range
Temperature coeffi-
cient
Resolution
Deactivated
–
–
–
Voltage
1 V to 5 V
0 V to 10 V
–
max. 16-bit
Current (4-wire transduc-
er)
0 mA to 20 mA
4 mA to 20 mA
–
max. 16-bit
Current (2-wire transduc-
er)
4 mA to 20 mA
–
max. 16-bit
Resistance
(3-wire connection)
Resistance
(2-wire connection)
150
Ω, 300
Ω
–
max. 15-bit
Resistance thermometer
(3-wire connection)
Resistance thermometer
(2-wire connection)
Pt 100 climatic range/
Pt 100 standard range
Pt 0.003850,
Pt 0.003916,
Pt 0.003902,
Pt 0.003920,
Pt 0.003851 EN 60751
max. 16-bit incl. sign
Ni 100 climatic range/
Ni 100 standard range
Ni 0.006180,
Ni 0.006720
max. 16-bit incl. sign