PROFIenergy
6.2 Behavior of the digital inputs
Digital input/Digital output module DIQ 16x24VDC/0.5A 8xM12 (6ES7143-5AH00-0BA0)
82
Equipment Manual, 08/2021, A5E38688112-AD
6.2
Behavior of the digital inputs
Display
The channel status LEDs are directly influenced by the signal level at the socket.
If the encoder supply is switched off, this causes the channel status LEDs to also switch off.
Response to error detection
All channels that are in pause mode on "PE_MODE_PROCEED" report their diagnostic status as
in productive mode.
The following applies for all channels which switch to a different pause mode:
•
Encoder supply switch-off upon the start of "pause" does not result in the "Short-circuit"
alarms.
•
During the "pause", error detection of "Short circuit" is not possible:
–
Alarms for errors already pending before the "pause" are retained.
–
After the "pause" is over, the error status is updated and incoming/outgoing errors are
reported correspondingly.
Mode parameter
The following table shows the "Mode" parameter.
Table 6- 1
Mode parameter
Element Code
Explanation
Mode
0
D
: PE_MODE_PROCEED
Proceed at "pause"
•
Value status "GOOD"
1
D
: PE_MODE_SHUTDOWN
Switch off at "pause"
•
Encoder supply U
S
switched off
1
•
Pause substitute value: 0
B
•
Value status "BAD"
3
D
: PE_MODE_LAST_VALUE
Last value at "pause"
•
Encoder supply U
S
switched off
1
•
Pause substitute value: Last input value
•
Value status "BAD"
4
D
: PE_MODE_SUBST_VALUE
Substitute value at "pause"
•
Encoder supply U
S
switched off
1
•
Pause substitute value: Configured pause substi-
tute value
•
Value status "BAD"
1
There are two encoder supplies, 1U
S
for Channels 0 to 7 and 2U
S
for Channels 8 to 15. At a "Pause"
the supplies can only be switched off if no channel is configured in PE_MODE_PROCEED.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......