IO-Link digital output module DQ 8x24VDC/2A 8xM12 (6ES7142-5AF00-0BL0)
Equipment Manual, 08/2021, A5E47926730-AB
15
Parameters/address space
4
4.1
Parameters
The following table shows the parameters for the DQ 8x24VDC/2A 8xM12 IO-Link digital
output module.
Table 4- 1
Parameters
Parameters
Value range
Default
Scope
ISDU
index
(decimal)
ISDU
subindex
(decimal)
Value
Dec
.
Hex
.
Diagnostics: Missing load volt-
age 2L+
Disable
0
0
Disable
Module
131
1
Enable
255 FF
Diagnostics: Short-circuit to
ground
Disable
0
0
Disable
Module
(Short-circuit of an
output to ground)
131
2
Enable
255 FF
Reaction to CPU/master STOP
Shutdown
0
0
Shutdown Module
131
3
Keep last value 2
2
Output substi-
tute value
3
3
Substitute value channel
0
0
0
0
Channel
131
4 ... 11
1
255 FF
4.2
Explanation of the parameters
Diagnostics: Missing load voltage 2L+
Enabling of the diagnostics for missing or insufficient load voltage 2L+.
Diagnostics: Short-circuit to ground
Enabling of the diagnostics for short-circuit of the output to ground.
Reaction to CPU/master STOP
With this parameter, you set the reaction of the digital outputs of the module after a
CPU/master STOP:
•
Shut down: The digital output is de-energized.
•
Keep last value: The last value of the digital output remains activated.
•
Output substitute value: The module outputs a configured substitute value.
Substitute value channel
With this parameter, you set substitute values for the digital outputs.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......