Representation of analog values
3.3 Representation of output ranges
Analog value processing
Function Manual, 06/2014, A5E03461439-AC
63
3.3
Representation of output ranges
The tables below set out the digitalized representation of the output ranges by bipolar and
unipolar range. The resolution is 16 bits.
Please see the device manuals for each analog output module for assignment of the values
to the specific output values in each measuring range.
Table 3- 5
Bipolar output ranges
Dec. value Output
value in %
Data word
Range
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
32511
117.589
0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Maximum output
value*
32511
117.589
0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Over range
27649
100.004
0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1
27648
100.000
0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0 Rated range
1
0.003617
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
0
0.000
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
-1
-0.003617
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
-27648
-100.000
1 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0
-27649
100.004
1 0 0 1 0 0 1 1 1 1 1 1 1 1 1 1 Under range
-32512
-117.593
1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0
-32512
-117.593
1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 Minimum output
value**
* When values > 32511 are specified, the output value is limited to 117.589 % or 0 % (0.0 V / 0.0 mA), depending on the
module used.
** When values < -32512 are specified, the output value is limited to -117.593 % or 0 % (0.0 V / 0.0 mA), depending on the
module used.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......