Cable shielding
4.2 Connecting the cable shielding for ET 200SP
Designing interference-free controllers
Function Manual, 06/2014, A5E03461486-AB
19
4.2
Connecting the cable shielding for ET 200SP
A special shield design has been developed for the shield connection of the signal lines of
the ET 200SP distributed I/O system. The connection element for the cable shield consists of
a shield terminal.
If the front connector is located in the module, the interference currents that occur are
diverted by the connection element via BaseUnit and mounting rail to the ground.
The shield terminal is plugged into a mount of the BaseUnit. The shield terminal allows the
low-impedance application of cable shields with minimum installation times. There is no need
for the otherwise standard connection of the cable shield at the cabinet entry.
The following figure shows a BaseUnit with shield terminal and shield support.
①
BaseUnit of ET 200SP
②
Shield terminal
③
Shield support with flat plug for terminal sockets
Figure 4-3
BaseUnit with shield terminal
Additional information
For more information on mounting the shield terminal, refer to the "Connecting cable shields"
chapter of the system manual ET 200SP Distributed I/O System
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......