Technical specifications
IO-Link digital input/digital output module DIQ 4+DQ 4x24VDC/0,5A 8xM8 (6ES7143-5BF00-0BL0)
24
Equipment Manual, 08/2021, A5E47925743-AB
Article number
6ES7143-5BF00-0BL0
Total current of the outputs
•
Current per module, max.
4 A
Cable length
•
unshielded, max.
30 m
Encoder
Connectable encoders
•
2-wire sensor
Yes
–
permissible quiescent current (2-wire sen-
sor), max.
1.5 mA
IO-Link
IO-Link protocol 1.1
Yes
Transmission rate
38.4 kBd (COM2)
Cycle time, min.
2.4 ms
Size of process data, input per module
1 byte
Size of process data, output per module
1 byte
Supported IO-Link profiles
common profile
Cable length unshielded, max.
20 m
Connection of IO-Link devices
•
Port type B
Yes
Interrupts/diagnostics/status information
Substitute values connectable
Yes; channel by channel, parameterizable
Alarms
•
Diagnostic alarm
Yes; Parameterizable
Diagnoses
•
Short-circuit
Yes; outputs to ground; encoder supply to
ground; module by module
Diagnostics indication LED
•
Channel status display
Yes; green LED
•
for module diagnostics
Yes; green/red LED
•
For load voltage monitoring
Yes; green LED
Potential separation
between the load voltages
Yes
Potential separation channels
•
between the channels
No
•
between the channels and the power supply
of the electronics
Yes
Isolation
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates
Suitable for safety-related tripping of standard
modules
Yes; From FS01
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......