Parameters/address space
4.3 Explanation of the parameters
Analog output module AQ 4xU/I 4xM12 (6ES7145-5ND00-0BA0)
20
Equipment Manual, 08/2021, A5E38687953-AC
4.3
Explanation of the parameters
Output type/range channel n
With this parameter, you set the output type or output range for the channel to control the
actuator.
Note
Unused channels
"Deactivate" unused channels in the parameter assignment to improve the power
consumption of the module.
A deactivated channel always returns the value "no voltage or current".
Diagnostics: Actuator supply short circuit to ground
Enabling of the diagnostics if a short-circuit of the actuator supply to ground occurs.
Diagnostics: Short circuit to ground
Enabling of the diagnostics if a short-circuit of the output to ground occurs.
Diagnostics: Wire break
Enabling of the diagnostics if the line to the actuator is broken.
Diagnostics: Underflow
Enabling of the diagnostics when the output value violates the underrange, falls below the
minimum output value or reaches the underflow.
Diagnostics: Overflow
Enabling of the diagnostics when the output value exceeds the overrange.
Reaction to CPU/master STOP
Adjusts the reaction of the module after a CPU/master STOP.
•
Shut down: The analog output is de-energized.
•
Keep last value: The last value of the analog output remains activated.
•
Output substitute value: The channel outputs a configured substitute value.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......