Interrupts, error messages, diagnostics and system alarms
5.2 Interrupts
IM 157-1 DP (6ES7157-1AA00-0AB0)
Equipment Manual, 08/2021, A5E32100641-AE
31
The following table is used to explain the channel error entries.
Description
Channel number
0 … 63: Channel number for channel error
0x8000: Entire submodule
Channel properties
Bits 0 to 7
00
H
: Free data type
01
H
: bit
02
H
: 2 bit
03
H
: 4 bit
04
H
: byte
05
H
: word
06
H
: double word
07
H
to FF
H
: Reserved
Bit 8
0: Channel
1: Channel group
Bit 9, 10
00
H
: Diagnostics
01
H
: Maintenance demanded
02
H
: Maintenance required
03
H
: Reserved
Bit 11, 12
00
H
: Channel error-free
01
H
: Incoming diagnostics
02
H
: Outgoing diagnostics
03
H
: Outgoing diagnostics, but other diagnostics are also
pending on this channel
Bits 13 to 15 00
H
: Reserved
01
H
: Input channel
02
H
: Output channel
03
H
: Input/output channel
Channel error type
Explanations are available in the device manuals, in the section "Diagnostic
alarms".
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......