Parameters/address space
4.2 Explanation of the parameters
CM 4xIO-Link 4xM12 (6ES7147-5JD00-0BA0)
2
3
Equipment Manual, 04/2021, A5E32352322-AE
Port configuration without S7-PCT
Requirement
You have enabled the check box "Port configuration without S7-PCT" for the configuration of
the IO-Link master in STEP 7.
Procedure
You configure the IO-Link master directly in STEP 7:
• Enabling of the diagnostics
• Configuration of the I/O data lengths per port
• Enabling of the Port Qualifier Information (PQI)
• Port mode:
–
Operation in "IO-Link autostart" mode (default)
–
Operation in "IO-Link manual" mode
–
Operated as DI
–
Operated as DQ
–
Disabled
Port configuration with S7-PCT
Requirement
You deselected the "Port configuration without S7-PCT" check box in the configuration of the
IO-Link master in STEP 7.
Procedure
You configure the port configuration of the IO-Link master using the port configuration tool
S7-PCT as of V3.2.
Port Qualifier Information (PQI)
You can enable the Port Qualifier Information (PQI) for your IO-Link master as of firmware
version V1.1.
Note
Port Qualifier Information (PQI)
If you have enabled the Port Qualifier Information (PQI), this information is always sent with
the size of 1 byte together with the input data of the IO-Link device.
The following figure show the structure of the PQI byte.
You enable a parameter by setting the corresponding bit to "1".
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......