2.2 Structure of PROFIBUS networks
PROFIBUS with STEP 7 V13
18
Function Manual, 12/2014, A5E03775446-AC
Selection criteria for networking
The table below includes selection criteria for electrical and optical networking of PROFIBUS
devices:
Table 2- 3
Selection criteria for electrical and optical networking
Criteria
Electrical
PROFIBUS
Optical network
with OLM
Optical network
with OBT
Transmission
medium
Shielded two-wire
line
●
–
–
POF
–
●
●
PCF
–
●
●
Glass
–
●
–
Distances
Max. network span
PROFIBUS DP:
9.6 km
PROFIBUS PA:
1.9 km
90 km
9.6 km
Between two devices up to 1 km
1)
up to 15 km
2)
up to 300 m
2)
Topology
Bus
●
–
–
Linear
–
●
●
Tree
●
●
●
Ring
–
●
●
Transmission
protocols
DP, PA
DP, PA
DP
Connection of
devices by means
of
OLM
–
●
–
Integrated interfaces ●
–
●
Bus terminal
●
–
●
Bus connector
●
–
–
Electrical network
segments can be
connected
●
●
–
● Suitable
– Not relevant for this application
1) Depending on data rate and type of service used
2) Depending on cable type used
Installation guideline for PROFIBUS networks
A PROFIBUS segment must be terminated at the start and end; passively with a connector
or actively with a bus terminating resistor.
The same principles apply to the installation of a PROFIBUS network as described in the
SIMATIC NET PROFIBUS networks
http://support.automation.siemens.com/WW/view/en/35222591
) manual.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......