Configuration control (option handling)
7.5 Behavior during operation
Distributed I/O system
80
System Manual, 08/2021, A5E31861578-AJ
7.5
Behavior during operation
Effect of discrepancy between station master and station option
For the online display and for the display in the diagnostics buffer (module OK or module
faulty), the station master is always used and not the differing station option.
Example: A module outputs diagnostics data. This module is configured in slot 4 in the
station master, but is inserted in slot 3 in the station option (missing module; see example in
the next section). The online view (station master) shows an incorrect module in slot 4. In the
real configuration, the module in slot 3 indicates an error via an LED display.
Response to modules that are not present
If modules are entered as not present in the control data record, the automation system
behaves as follows:
•
Modules designated as not present in the control data record do not supply diagnostics
and their status is always OK. The value status is OK.
•
Direct writing access to the outputs that are not present or writing access to the process
image of outputs that are not present: Remains without effect; no access error is signaled.
•
Direct reading access to the inputs that are not present or reading access to the process
image of inputs that are not present: Value "0" is supplied; no access error is signaled.
•
Write data record to module that is not present: Remains without effect; no error is
signaled.
•
Read data record from module that is not present: The output parameter STATUS of the
instruction RDREC supplies the value 80A3
H
"General CM error".
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......