Representation of analog values
B.2 Representation of analog values in the current output ranges
Analog output module AQ 4xU/I 4xM12 (6ES7145-5ND00-0BA0)
36
Equipment Manual, 08/2021, A5E38687953-AC
Table B- 7
Current output range 4 mA to 20 mA
Values
Current output range
Range
Dec.
Hex.
4 mA to 20 mA
118.5149%
32767
7FFF
21 mA
Maximum output value
29377
72C1
106.25%
29376
72C0
21 mA
Overrange
27649
6C01
20 mA + 578.7 nA
100%
27648
6C00
20 mA
Nominal range
75%
19008
4A40
16 mA
0.003617%
1
1
4 mA + 578.7 nA
0%
0
0
4 mA
-1
FFFF
3.9995 mA
Underrange
-2.5%
-692
FD4C
3.6 mA
-693
FD4B
3.6 mA
Minimum output value
-118.519%
-32768
8000