OPC UA communication
9.4 Using the S7-1500 CPU as an OPC UA client
Communication
Function Manual, 05/2021, A5E03735815-AJ
329
Data blocks of client interface
The following data blocks belong to the "Productionline" client interface:
•
Productionline_Configuration
A data block for the configuration.
In the example, this data block is called "Productionline_Configuration".
The data block already contains all system data types that are needed for the instructions
of the OPC UA client.
In addition, the data block contains general default values for parameter assignment of
the connection to an OPC UA server.
If you are working with connection parameter assignment, this data block will be filled.
•
ProductionLine_Data
A data block for the PLC tags that you have entered in the client interface editor.
In the example, this data block is called "Productionline_Data".
The figure below shows the data block.
Figure 9-67 "Productionline_Data" data block
Use the "Productionline_Data" data block in your user program and access the read values
of the "NewProduct" and "ProductNumber" PLC tags. This is explained in the following
section using an example.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......