Alarms
6.5 Example program for program alarms
Diagnostics
90
Function Manual, 11/2019, A5E03735838-AF
Define tags for signal acquisition
The following table shows the tags that are used in this example. Define these tags in the
standard tag table. The standard tag table is available in the project tree under "PLC tags".
Table 6- 2
Tags for fill level alarms
Name
Data type
Description
max
BOOL
Tag for maximum fill level
If "max" = 1, the maximum fill level is exceeded.
min
BOOL
Tag for minimum fill level
If "min" = 1, the minimum fill level is undershot.
The figure below shows the standard tag table with the defined tags "max" and "min".
Figure 6-11 Define tags