PROFIenergy
7.2 Response of the analog input module
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Equipment Manual, 08/2021, A5E32350124-AG
45
Mode parameter
The following table shows the "Mode" parameter.
Table 7- 1
Mode parameter
Element Code
Explanation
Mode
0
D
: PE_MODE_PROCEED
Proceed at "pause"
•
Value status "GOOD"
1
D
: PE_MODE_SHUTDOWN
Switch off at "pause"
•
Encoder supply U
S
switched off
1
•
Pause substitute value: 7FFF
H
•
Value status "BAD"
3
D
: PE_MODE_LAST_VALUE
Last value at "pause"
•
Encoder supply U
S
switched off
1
•
Pause substitute value: Last input value
•
Value status "BAD"
4
D
: PE_MODE_SUBST_VALUE
Substitute value at "pause"
•
Encoder supply U
S
switched off
1
•
Pause substitute value: Configured pause sub-
stitute value
•
Value status "BAD"
1
Encoder supply U
S
is only provided for measurement type current and voltage and can only be
deactivated in these measurement types.