Distributed I/O system
System Manual, 08/2021, A5E31861578-AJ
21
Application planning
3
3.1
Hardware configuration
Mechanical maximum configuration
The following tables show the rules of the mechanical configuration. As soon as one of the
following rules applies, the maximum configuration has been reached.
Table 3- 1
Maximum mechanical configuration - on ET 200AL interface module
Properties
Rule (max.)
Interface modules
as of firmware ver-
sion V1.0.0
Interface modules
as of firmware ver-
sion V1.0.1
Number of ET 200AL I/O modules in the configuration
32
Number of ET-Connection outlets
2
Number of I/O modules per ET-Connection outlet
16
Spatial extension per ET-Connection line
160 m
240 m
Cable length between the modules
10 m
15 m
Table 3- 2
Maximum mechanical configuration - on ET 200SP with interface module
Properties
Rule (max.)
Interface modules
as of firmware ver-
sion V3.0.0
Interface modules
as of firmware ver-
sion V3.3.0
Number of ET 200AL I/O modules in the configuration
16
Number of ET-Connection outlets
1
Spatial extension ET-Connection line
160 m
240 m
Cable length between the modules
10 m
15 m
Table 3- 3
Maximum mechanical configuration - on ET 200SP with CPU
Properties
Rule (max.)
CPUs with firmware version as of V2.0.0
Number of ET 200AL I/O modules in the configuration
16
Number of ET-Connection outlets
1
Spatial extension ET-Connection line
240 m
Cable length between the modules
15 m
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......