Technical specifications
7.1 Specifications
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
79
6ES7146-5FF00-0BA0
Digital inputs
Number of digital inputs
4
Input characteristic according to IEC 61131
Type 1
Number of simultaneously controllable
inputs
all mounting positions
up to 55 °C, max.
4
Input voltage
Rated value (DC)
24 V
for signal "0"
-30 to +5 V
for signal "1"
+15 to +30 V
Input current
for signal "1", typ.
4,85 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizable
Yes
at "0" to "1", min.
0,8 ms
at "0" to "1", max.
12,8 ms
at "1" to "0", min.
0,8 ms
at "1" to "0", max.
12,8 ms
Cable length
unshielded, max.
30 m
Digital outputs
Number of digital outputs
2
in groups of
2
Short-circuit protection
Yes; per channel, electronic
Response threshold, typ.
10 A; measured at M-switch, threshold for P-
switch is higher
Open-circuit detection
Yes; per channel, only detects when output is off
Overload protection
Yes
Response threshold, typ.
3,4 A; measured at P-switch
Limitation of inductive shutdown voltage to
P-switch: -26 V DC referenced to 2M, M-switch:
+48 V DC referenced to 2M
Switching capacity of the outputs
on lamp load, max.
10 W
Load resistance range
lower limit
12
Ω
upper limit
2 k
Ω
Output current
for signal "1" rated value
2 A
for signal "0" residual current, max.
0,5 mA
Switching frequency
with resistive load, max.
30 Hz
with inductive load, max.
0,1 Hz
on lamp load, max.
10 Hz
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......