Programming
4.3 Time-based IO
High-precision input/output with Time-based IO
Function Manual, 11/2019, A5E33454822-AC
35
Error code
Meaning
Solution
(DW#16#...)
10080000
At least one of the hardware identifiers does not belong to
a TIO module.
Check the values of input parameters HWID_1
to HWID_8. Specify the hardware identifier of
the TIO module from its module properties in the
hardware configuration.
10090000
HWID_1 is not a valid hardware identifier.
Possible cause:
No module with this hardware identifier available.
Check the value of the respective input
parameter. In each case, specify the hardware
identifier of the TIO module from its module
properties in the hardware configuration. An
internal system constant of data type
Hw_SubModule is available for the symbolic
addressing.
100A0000
HWID_2 is not a valid hardware identifier.
Possible cause:
No module with this hardware identifier available.
100B0000
HWID_3 is not a valid hardware identifier.
Possible cause:
No module with this hardware identifier available.
100C0000
HWID_4 is not a valid hardware identifier.
Possible cause:
No module with this hardware identifier available.
100D0000
HWID_5 is not a valid hardware identifier.
Possible cause:
No module with this hardware identifier available.
100E0000
HWID_6 is not a valid hardware identifier.
Possible cause:
No module with this hardware identifier available.
100F0000
HWID_7 is not a valid hardware identifier.
Possible cause:
No module with this hardware identifier available.
10100000
HWID_8 is not a valid hardware identifier.
Possible cause:
No module with this hardware identifier available.
10110000
The value at input parameter PIP_PART is outside the
valid range of 1 ... 31.
Correct the value at the PIP_PART input
parameter.
10120000
The value "2" is configured at the input parameter
PIP_Mode, while the value > 1 (reduction ratio) is
configured at the static parameter AppCycleFactor.
Correct the value at the PIP_Mode input
parameter. PIP_Mode with the value "2" does
not allow a reduction ratio.
x0130000
MC-Servo (OB91) is not isochronous to the bus cycle
time.
Correct the value of the cycle time of the MC-
Servo to the value of the bus cycle time.
Note:
Calling TIO instructions in an OB of the type
"MC-PostServo" with reduction ratio "MC-Servo"
can result in incorrect calculation of time
stamps.
x014xxxx
An error has occurred when reading the data record. The
low word xxxx indicates the error information of the
instruction RDREC.
Read the description of the instruction RDREC
in the STEP 7 (TIA Portal) information system.
x0FF0000
General internal error.
—
* Available only when "0" is selected for the input parameter PIP_Mode.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......