OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
Function Manual, 05/2021, A5E03735815-AJ
311
Monitored Item Service Set
CreateMonitoredItems
ModifyMonitoredItems
DeleteMonitoredItems
SetMonitoringMode
SetTriggering
Subscription Service Set
CreateSubscription
ModifySubscription
DeleteSubscriptions
Publish
Republish
SetPublishingMode
9.3.7.6
Subscription diagnostics
Information about a subscription
S7-1500 CPUs as of firmware version V2.8 are able to create an entry in the diagnostic buffer
at state changes of a subscription.
The diagnostic buffer displays the new state; exception: "KeepAlive".
Requirement
In the OPC UA properties of the CPU, the option "Subscriptions: Change of status" (OPC UA >
Server > Diagnostics) is selected.
Example
An OPC UA client is connected to an S7-1500 CPU as OPC UA server and generates a
subscription in the server.
The diagnostic options for subscriptions are selected in the OPC UA properties of the CPU.
The "Creating" and "Normal" states are entered one after the other with the corresponding
subscription ID in the diagnostic buffer.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......