Parameter assignment/addressing
3.2 Device name and IP address
PROFINET with STEP 7
58
Function Manual, 05/2021, A5E03444486-AL
General procedure
To assign PROFINET device names, you must first detect the IO devices available online. With
this procedure, it matters whether the MAC addresses are known or unknown. This results in
a general procedure in two steps:
1.
Detecting the IO devices available online
2.
Assigning configured PROFINET device names to the IO devices available online
Requirements
•
You are in the network view.
•
There is an online connection to the devices.
Procedure (step 1)
To detect IO devices available online from the I/O communication table, follow these steps:
1.
Optional: Entered known MAC addresses in the "MAC address" column. After every valid
entry, the check box under "Assign device" is selected for the relevant row.
Note
You can enter, insert or import the MAC address in different formats. The correct format is
automatically entered in the cell. The following entries are supported and then converted
to the required format:
•
"08:00:06:BA:1F:20"
•
"08 00 06 BA 1F 20"
•
"080006BA1F20"
The formats used in the example are automatically converted to "08-00-06-BA-1F-20".
2.
Click "Check devices" to start the check of the IO devices available online.
3.
Set the PG/PC interface in the dialog window and click "Start".
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......