IO-Link I/O modules
System Manual, 08/2021, A5E48755395-AB
47
Maintenance
8
8.1
Replacing modules
Replacing IO-Link I/O modules
The replacement of a module is not permitted during ongoing operation.
WARNING
Property damage can occur
If you remove/insert modules while the power is connected, this can lead to undefined
states in your system.
The IO-Link I/O module may be damaged as a result.
Only remove or replace modules when the power is disconnected.
Always comply with the required standards and safety guidelines when configuring a
system.
If you use the restore function of the master, the master automatically provides the saved
parameters to the new module after module replacement. You have the following setting
options for module replacement:
•
"Backup&Restore"
You have set the master port to "Backup&Restore". The new module behaves like the
replaced module because the master has saved the last parameter change using the
backup function.
•
"Restore"
You have set the master port to "Restore". The new module applies the parameter settings
that were saved in the master at the time of the last back-up.