background image

MODEL: R1M-GH

R1M-GH SPECIFICATIONS

ES-5657 Rev.11   Page 1/9

Remote I/O R1M Series

THERMOCOUPLE & DC INPUT MODULE

(16 points)
Functions & Features
• 16-point thermocouple or DC inputs
• Easy system expansion via Modbus RTU

40
(1.57)

115

(4.53)

mm (inch)

175 (6.89)

MODEL: R1M-GH2T-[1][2]

ORDERING INFORMATION

• Code number: R1M-GH2T-[1][2]
  Specify a code from below for each [1] and [2].
(e.g. R1M-GH2T-M2/Q)
• Specify the specification for option code /Q
(e.g. /SET)

FIELD TERMINAL TYPE

T: M3 screw terminals

[1] POWER INPUT

AC Power

M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

EX-FACTORY SETTING

/SET: Preset according to the Ordering Information Sheet
 (No. ESU-5657-A)

RELATED PRODUCTS

• Resistor module (model: REM3-250)
• R1X configurator software (model: R1CON)
Downloadable at M-System’s web site.

A dedicated cable is required to connect the module to the
PC.  Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.

GENERAL SPECIFICATIONS

Connection
  Power input, transmission: Euro type connector terminal
  RS-232-C: 9-pin D-sub connector (male)
  (Lock screw No. 4-40 UNC)
  I/O: M3 screw terminals
Isolation: Input to RS-232-C or RS-485 to power
Node address setting: Rotary switch; 1 – F (15 nodes)
RUN indicator LED: Green light blinks in normal conditions.

COMMUNICATION

Baud rate: 38.4 kbps
Communication: Half-duplex, asynchronous, no procedure
Protocol: Modbus RTU
Refer to Modbus Protocol Reference Guide (EM-5650) for
supported functions.
■ RS-232-C
Standard: Conforms to RS-232-C, EIA
Transmission distance: 10 meters max.
■ RS-485
Standard: Conforms to RS-485, EIA
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable (CPEV-S
0.9 dia.)

INPUT SPECIFICATIONS

Input: Thermocouple or DC input, 16 points
(Common negative for DC input)
Measuring Range:
  ±20 V, ±5 V, ±1 V, ±0.8 V, ±0.2 V, ±50 mV, ±10 mV
Input resistance: 300 kΩ
Thermocouple types: PR, K, E, J, T, B, R, S, C, N, U, L, P
Sampling rate: 100 millisec./16 points
• Trigger input: Dry contact; ON detected at ≤1.5 V
Sensing: Approx. 5 V DC @ 1 mA

INSTALLATION

Power consumption
•AC: Approx. 10 VA
•DC: Approx. 7 W
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lb)

Summary of Contents for R1M-GH2T Series

Page 1: ...r for applicable cable types GENERAL SPECIFICATIONS Connection Power input transmission Euro type connector terminal RS 232 C 9 pin D sub connector male Lock screw No 4 40 UNC I O M3 screw terminals I...

Page 2: ...1000 454 to 1832 0 7 J IC 210 to 1200 346 to 2192 0 7 T CC 270 to 400 454 to 752 1 0 B RH 100 to 1820 212 to 3308 0 7 2 R 50 to 1760 58 to 3200 0 7 1 S 50 to 1760 58 to 3200 0 7 1 C WRe 5 26 0 to 2320...

Page 3: ...RD 3 Received Data AB SG 5 Signal Common CB CS 7 Clear to Send CA RS 8 Request to Send 1 Not Used 4 DO NOT connect Connecting may 6 cause malfunctions 9 1 5 6 9 RS 232 C INTERFACE MODBUS WIRING CONNEC...

Page 4: ...not at the end remove the jumper pin Remark 1 This device is not designed to cancel noise included in the input signals Be careful to eliminate such noise by using shielded cables Remark 2 Be sure to...

Page 5: ...ted data from the field by the slave 05 Force Single Coil X Digital output from the slave 06 Preset Single Registers X General purpose register within the slave 07 Read Exception Status 08 Diagnostics...

Page 6: ...dware version No 538 545 Y Y Y Y B16 Firmware version No Holding Register 1 16 I Reserved for AO in 4X 17 48 F Reserved for AO in engineering unit 145 160 Y Y I I O type No 161 176 Y I Burnout type 16...

Page 7: ...inputs 1 16 1 8 for J3 The following list shows the names and descriptions of each bit INPUT TYPE RANGE A D DATA Decimal DC 20V 20000 5V 5000 1V 10000 0 8V 8000 0 2V 20000 50mV 5000 10mV 10000 Thermoc...

Page 8: ...0 C 0X16 R 50 to 1760 C 0X17 S 50 to 1760 C 0X18 C WRe 5 26 0 to 2320 C 0X19 N 270 to 1300 C 0X1A U 200 to 600 C 0X1B L 200 to 900 C 0X1C P Platinel II 0 to 1395 C R1M J3 RTD input 0X30 JPt 100 JIS 89...

Page 9: ...5 TC DC Inputs model R1M GH Contact Inputs model R1M A1 Contact Outputs model R1M D1 When the cable distance between the PC and the R1Ms is long insert an RS 232 C RS 485 Converter for isolation RS 23...

Reviews: