background image

MODEL: R1M-GH

R1M-GH SPECIFICATIONS

ES-5657 Rev.11   Page 5/9

MODBUS COMMUNICATION

 

COMMUNICATION PARAMETERS

 

 

PARAMETER 

SPECIFICATION

Data Mode

RTU

Baud Rate

9600 / 19200 / 38400 (*) bps

Parity 

None / Odd (*) / Even

Bit Length

8

Stop Bit

1 (*) / 2

Node Address

1 (*) to 15

Floating Point Data

N/A

Interface

RS-232-C/ RS-485

(*)

Ex-factory setting

 

FUNCTION CODES & SUPPORTED CODES

CODE 

NAME 

 

01 

Read Coil Status

Digital output from the slave

 

02 

Read Input Status

Status of digital inputs to the slave

 

03 

Read Holding Registers

General purpose register within the slave

 

04 

Read Input Registers

Collected data from the field by the slave

 

05 

Force Single Coil

Digital output from the slave

 

06 

Preset Single Registers

General purpose register within the slave

 

07 

Read Exception Status

 

08 

Diagnostics

 

09 

Program 484

 

10 

Poll 484

 

11 

Fetch Comm. Event Counter 

 

Fetch a status word and an event counter

 

12 

Fetch Comm. Event Log

 

A status word, an event counter, a message count and a field of event bytes

 

13 

Program Controller

 

14 

Poll Controller

 

15 

Force Multiple Coils

Digital output from the slave

 

16 

Preset Multiple Registers 

General purpose register within the slave

 

17 

Report Slave ID

 

Slave type / ‘RUN’ status

 

18 

Program 884/M84

 

19 

Reset Comm. Link

 

20 

Read General Reference

 

21 

Write General Reference

 

22 

Mask Write 4X Register

 

23 

Read/Write 4X Register

 

24 

Read FIFO Queue

Summary of Contents for R1M-GH2T Series

Page 1: ...r for applicable cable types GENERAL SPECIFICATIONS Connection Power input transmission Euro type connector terminal RS 232 C 9 pin D sub connector male Lock screw No 4 40 UNC I O M3 screw terminals I...

Page 2: ...1000 454 to 1832 0 7 J IC 210 to 1200 346 to 2192 0 7 T CC 270 to 400 454 to 752 1 0 B RH 100 to 1820 212 to 3308 0 7 2 R 50 to 1760 58 to 3200 0 7 1 S 50 to 1760 58 to 3200 0 7 1 C WRe 5 26 0 to 2320...

Page 3: ...RD 3 Received Data AB SG 5 Signal Common CB CS 7 Clear to Send CA RS 8 Request to Send 1 Not Used 4 DO NOT connect Connecting may 6 cause malfunctions 9 1 5 6 9 RS 232 C INTERFACE MODBUS WIRING CONNEC...

Page 4: ...not at the end remove the jumper pin Remark 1 This device is not designed to cancel noise included in the input signals Be careful to eliminate such noise by using shielded cables Remark 2 Be sure to...

Page 5: ...ted data from the field by the slave 05 Force Single Coil X Digital output from the slave 06 Preset Single Registers X General purpose register within the slave 07 Read Exception Status 08 Diagnostics...

Page 6: ...dware version No 538 545 Y Y Y Y B16 Firmware version No Holding Register 1 16 I Reserved for AO in 4X 17 48 F Reserved for AO in engineering unit 145 160 Y Y I I O type No 161 176 Y I Burnout type 16...

Page 7: ...inputs 1 16 1 8 for J3 The following list shows the names and descriptions of each bit INPUT TYPE RANGE A D DATA Decimal DC 20V 20000 5V 5000 1V 10000 0 8V 8000 0 2V 20000 50mV 5000 10mV 10000 Thermoc...

Page 8: ...0 C 0X16 R 50 to 1760 C 0X17 S 50 to 1760 C 0X18 C WRe 5 26 0 to 2320 C 0X19 N 270 to 1300 C 0X1A U 200 to 600 C 0X1B L 200 to 900 C 0X1C P Platinel II 0 to 1395 C R1M J3 RTD input 0X30 JPt 100 JIS 89...

Page 9: ...5 TC DC Inputs model R1M GH Contact Inputs model R1M A1 Contact Outputs model R1M D1 When the cable distance between the PC and the R1Ms is long insert an RS 232 C RS 485 Converter for isolation RS 23...

Reviews: