Description:
Displays the internal resistance of the power unit (IGBT and line resistance).
Description:
Sets the shutdown thresholds for the ground fault monitoring.
The setting is made as a percentage of the maximum current of the power unit (r0209).
Index:
[0] = Threshold at which precharging starts
[1] = Threshold at which precharging stops
Dependency:
Refer to: p1901
Refer to: F30021
Note:
This parameter is only relevant for chassis power units.
Description:
Displays the actual maximum output current of the power unit taking into account derating factors.
Description:
Sets the response to a thermal overload condition of the power unit.
The following quantities can result in a response to thermal overload:
- heat sink temperature (r0037[0]).
- chip temperature (r0037[1]).
- power unit overload I2t (r0036).
Possible measures to avoid thermal overload:
- reduce the output current limit r0289 and r0067 (for closed-loop speed or torque control) or the output frequency (for
U/f control) indirectly via the output current limit and the intervention of the current limiting controller).
- reduce the pulse frequency.
A reduction, if parameterized, is always realized after an appropriate alarm is output.
Value:
0:
Reduce output current or output frequency
1:
No reduction shutdown when overload threshold is reached
2:
Reduce I_output or f_output and f_pulse (not using I2t)
3:
Reduce the pulse frequency (not using I2t)
12:
I_output or f_output and automatic pulse frequency reduction
13:
Automatic pulse frequency reduction
r0238
Internal power unit resistance / PU R internal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [ohm]
- [ohm]
- [ohm]
p0287[0...1]
Ground fault monitoring thresholds / Gnd flt threshold
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.0 [%]
100.0 [%]
[0] 6.0 [%]
[1] 16.0 [%]
r0289
CO: Maximum power unit output current / PU I_outp max
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2002
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p0290
Power unit overload response / PU overld response
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8021
Min Max
Factory
setting
0 13
2
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......